TCA-AO Intrinsically safe isolating driver
Comprehensive parameter
Standard accuracy: ±0.05% FS
Temperature drift: Typical value < ±1μA/10℃
Powering or storage time drift: ±2μA (180 days)
Influence of load change: ±2μA
Influence between the channels: Maximum: 2μA
Response time: <1ms
Stabilization time after power-on: <1s
Maximum Bearable Experimental voltage: For input-output-power supply: 2.5 kV AC (50 Hz, 1 min., test voltage)
TCA-AO applies to connection between output signals of the control system and the field intrinsically safe circuit. After being isolated, it transmits 4-20 mA analog signals to the field actuator.
Category:
Keywords:
Product Details
■ Overview
TCA-AO applies to connection between output signals of the control system and the field intrinsically safe circuit. After being isolated, it transmits 4-20 mA analog
signals to the field actuator. It can also transmit HART communication signals in a superimposing manner while transmitting the analog signals (optional).
Accuracy ±0.05% FS Temperature drift (typical value) <±1μA/10 ℃.-20 ~ +80 ℃ temperature test, typical value < ±10 μA.
The test preheating time is 0.
Output signals can be extended to 0~20 mA.
Output self-adaptive load: 0~800 Ω. High limit of the output current is 25 mA. Load change error < ±2 μA/800 Ω; impact of load open circuit on the other output < ±2 μA.
The power supply range can be chosen from within range of 20~42VDC or 15~42VDC.
See the “Technical Data Sheet” in the specifications for current consumption or other functional indices.
There is no power light on the instrument panel. The power supply indicator is replaced by a model printed on the instrument panel. After the power is on, the
model on the panel becomes illuminated by means of the LED backlight.
Clamping type structure, a 35 mm DIN standard guide rail clamping type installation is used. Screw terminal, the wire is connected and fastened by M3 screws.
■ Model, model selection and ordering

Model selection example
Example 1. TCA-AOH11-AA-V1……1-input & 1-output,Intrinsically safe isolating driver,HART communication (4~20mA input,4~20mA intrinsic safety output,
terminal power supply 20~42VDC)
Example 2. TCA-AO22-BB-V1……2-input & 2-output,Intrinsically safe isolating driver (0~20mA input,0~20mA intrinsic safety output, terminal power supply 20~42VDC)
Example 3. TCA-AO33-AA-V2……3-input & 3-output,Intrinsically safe isolating driver(4~20mA input,4~20mA intrinsic safety output, guide rail power supply 20~42VDC)
Note: if you select products with guide rail power supply, please order the special power supply DIN guide rail as well.
Optional accessories: Special power supply DIN guide rail (1 m/pc) PSDR-9000
■ Block diagram/wiring diagram





■ Technical Data

Related Application
Hot Products