TC-TP Universal Signal Isolator Safety Barrier
Thermal resistance of Pt100, Cu50
Thermocouple of K, E, S, B
Resistance (maximum range 0~500 Ω)
Millivolt (maximum range 0~100 mv)
Transmitter (power distributor), current 4~20 mA or 0~20 mA
Current source 4~20 mA or 0~20 mA
TC-TP is used to input the current, thermal resistance, thermocouple, millivolt, sliding resistance and other signals
Category:
Keywords:
Product Details
■ Overview
TC-TP is used to input the current, thermal resistance, thermocouple, millivolt, sliding
resistance and other signals; provide the power distribution for the field transmitter and
receive the current signal input from the transmitter. Following isolation, it converts it into
the standard current signal and then transmits it to the control systems or other instruments.
The universal signal isolator switches signal inputs such as power distribution, current,
thermocouple, thermal resistance, millivolt and sliding resistance in various wiring modes.
Input signals can complete the configuration settings by means of the calibration software
and interfaces (accessories optional). Configuration parameters only include three items, i.e.
signals (or graduation), null point and full scale, which can be conducted in the state of no
power. The accuracy after normal use is greater than 0.03%FS. Input is open circuit or short
circuit, the output is above the high limit or below the low limit, the default value of the
configuration is output greater than 22mA. The configuration can also be reset.
Thermal resistance input range: 10 Ω~400 Ω; minimum resolution: ±2 mΩ; stability: ±3 mΩ.
When the compensating lead error of three-wire input is not less than 50 ℃ range (Pt100),
the additive error is not more than ±0.02 ℃.
Thermocouple input voltage range: 4~80 mV; minimum resolution: ±1 μV; stability:
±2 μV. The additive error of cold junction compensation is not more than ±1 ℃.
The maximum range of the sliding resistance is 0~500Ω. When the range is less than 50Ω,
the three-wire form should be used for connections. Input mode offsets the lead error.
Accuracy ±0.05% FS
The maximum range of DC millivolt should be 0~100mVDC, and the minimum should be
0~5mVDC, with the accuracy of ±0.05%FS. Minimum resolution: 1μV; stability: 2μV;
temperature drift: ±20PPM/℃.
The power distribution voltage is more than 16VDC. The power distribution output clamp
current can be customized as required, but must be specified upon ordering. The factory
default is 28 mA (±2 mA).
For power distribution or current input/output, the typical accuracy value is ±0.05% FS;
and the temperature drift is ±0.1 μA/℃.
The output signal can be extended from 4~20 mA to 0~20 mA.
The output self-adaptive load is 0~800 Ω (Note: 1-input & 3-output load is 0~550 Ω, and
1-input & 4-output load is 0~350 Ω).
The power supply range can be chosen from within range of 20~42VDC or 15~42VDC.
See the “Technical Data Sheet” in the specifications for current consumption or other
functional indices.
The instrument panels for universal signal isolators include two types: LCD and LED
backlight. The LCD can display the input value, output value, or the position number
required by the user. In case of no LCD, the LED backlight design shall be used for the
instrument panel. After the power is on, the model on the panel becomes illuminated by
means of the LED backlight.
Clamping type structure, a 35 mm DIN standard guide rail clamping type installation is
used. Screw terminal, the wire is connected and fastened by M3 screws.
■ Model, model selection and ordering
Model selection example
Example 1. TC-TP11-UB-V1……1-input & 1-output, Universal signal isolator (user must set parameters:with power distribution, 0-20mA input, 0-20mA output, terminal power supply 20-42VDC)
Example 2. TC-TPX13-UA-V1……1-input & 3-output, Universal signal isolator, with displays (user must set parameters:4-20mA input, 4-20mA output, Terminal power supply 20-42VDC)
Example 3. TC-TPX22-UA-V2……2-input & 2-output, Universal signal isolator, with displays (user must set parameters:Pt100, 0-300℃ input, 4-20mA output, guide rail power supply 20-42VDC)
Note: if you select products with guide rail power supply, please order the special power supply DIN guide rail as well.
Optional accessories:
Calibrated software CRFW-2000 for winXP and win7 PC
Calibration interface CR-2206 for general products
General product Android calibration interface FAIF-1904
Special power supply DIN guide rail (1 m/pc) PSDR-9000
■Block diagram/wiring diagram